Heat Loss Calculator

Estimate steady-state heat loss by building component. Enter each area and U-value, the indoor–outdoor temperature difference, and an optional simplified ventilation estimate.

Wall area / Wall U-value (W/m²·K)
Roof area / Roof U-value (W/m²·K)
Window area / Window U-value (W/m²·K)
Floor area / Floor U-value (W/m²·K)

Simplified steady-state estimate, not a heating-system size recommendation. Use U-values and air changes from reliable building data. This omits thermal bridges, solar/internal gains, moisture, wind, ducts and dynamic operation. Have a qualified energy professional review assumptions before making building or equipment decisions.

How do you calculate heat loss through a building component?

For transmission, multiply area by U-value and temperature difference: watts = m² × W/(m²·K) × K. A component with U = 1, area 10 m² and a 20 K difference contributes 200 W. Ventilation is estimated separately from room volume and air changes.

Guide

Using Heat Loss Calculator

This heat loss calculator adds up how fast a room or small building loses heat in a steady, cold-weather situation. You enter the area and U-value of the walls, roof, windows and floor, the temperature gap between inside and outside, and an optional room volume with air changes per hour. It returns watts for each part, a ventilation estimate and a total in watts and BTU/h. It is a rough sketch for learning and comparing options, not a tool for sizing a boiler or heat pump.

How to use it

  1. Pick the units first. Choose square metres or square feet for all areas, kelvin or Fahrenheit for the temperature gap, and cubic metres or cubic feet for the room volume.
  2. Type the indoor minus outdoor temperature difference. A gap of 20 means the inside is 20 K (or 20 degrees F) warmer than the outside.
  3. For each of the four parts (wall, roof, window, floor) enter its area and its U-value in W/m²·K. Type 0 in both boxes for a part that does not exist.
  4. Enter the room volume and the air changes per hour. Use 0 and 0 if you want to leave ventilation out.
  5. Press Estimate heat loss, then Copy estimate if you want to paste the rows into a note.

Worked examples

The built-in example: one wall

You enter
Temperature difference
20 K
Wall
10 m² at U = 1
Other parts and ventilation
all 0
You get
Wall
200 W
Total
200 W (682.43 BTU/h)

Area times U-value times the temperature gap: 10 × 1 × 20 = 200 W. The other rows stay at zero.

Run through the tool’s own code.

A small room with all four parts and some air exchange

You enter
Temperature difference
20 K
Walls
30 m² at U 0.3
Roof
20 m² at U 0.2
Windows
4 m² at U 1.4
Floor
20 m² at U 0.25
Ventilation
50 m³ at 0.5 air changes per hour
You get
Walls
180 W
Roof
80 W
Windows
112 W
Floor
100 W
Total transmission
472 W
Ventilation
165 W
Total
637 W (2,173.53 BTU/h)

The four parts add up to 472 W. Ventilation is 0.33 × 50 × 0.5 × 20 = 165 W. The sum is 637 W. Notice the small window loses more than the much larger roof.

Run through the tool’s own code.

A Fahrenheit temperature gap

You enter
Temperature difference
36 degrees F
Wall
10 m² at U = 1
You get
Wall
200 W
Total
200 W (682.43 BTU/h)

A gap of 36 degrees F is multiplied by 5/9 and becomes 20 K. The tool does not add the 32 offset, because this is a difference and not a thermometer reading.

Run through the tool’s own code.

US customary areas and volume

You enter
Temperature difference
20 K
Wall
100 ft² at U = 0.5 W/m²·K
Ventilation
1,000 ft³ at 1 air change per hour
You get
Wall
92.9 W
Ventilation
186.89 W
Total
279.79 W (954.7 BTU/h)

The tool converts 100 ft² to 9.290304 m² and 1,000 ft³ to 28.3168 m³. The U-value still has to be typed in W/m²·K, even when areas are in square feet.

Run through the tool’s own code.

When it helps

  • Compare how much of a room's heat loss goes through the windows and how much through the walls before thinking about upgrades.
  • See what happens to the total if the roof U-value drops from an old figure to a better one.
  • Check a homework or course exercise on conduction and ventilation losses.
  • Get a first idea of how much ventilation adds in a small, draughty room compared with a tight one.
  • Turn a list of areas and U-values from an energy report into one watt figure you can talk about.

Limits to keep in mind

  • Transmission is area × U-value × temperature gap, and ventilation uses a fixed factor of 0.33 × volume × air changes per hour × temperature gap. Both are steady-state simplifications.
  • Thermal bridges, sun and internal heat gains, wind, damp, ducts, heating-up time and local design temperatures are not modelled.
  • All twelve numeric boxes must be filled (use 0 for unused parts). Gaps go up to 1,000, areas to 100,000,000, U-values to 1,000, volume to 1,000,000,000 and air changes to 100.
  • Do not use the result to size a boiler, heat pump or radiator, and do not use it to predict an energy bill. A qualified energy professional should check the assumptions behind any equipment choice.

Tips

  • Take U-values from product data, a survey or an energy certificate rather than guessing. Small U-value errors on a large wall move the answer a lot.
  • Keep every U-value in W/m²·K even if you switch the area to square feet; the tool never converts the U-value.
  • Run the sum twice, once with ventilation at 0 and once with your best air-change figure, to see how much the draughts matter.
  • Use the Fahrenheit option only for a temperature difference, such as 36 degrees F between rooms, never for a thermometer reading like 68 degrees F.

Sources

Frequently asked questions

What formula does the heat loss calculator use?

For each wall, roof, window and floor it multiplies area (m²), U-value (W/m²·K) and temperature gap (K) to get watts. Ventilation is 0.33 × room volume (m³) × air changes per hour × temperature gap. The total is the four parts plus ventilation, also shown in BTU/h.

Where does the 0.33 in the ventilation term come from?

It is a rounded value for the heat capacity of air per cubic metre when the air change rate is given per hour. The UK government's SAP 10.2 dwelling energy method, listed below, uses the same 0.33 multiplier in its ventilation heat loss line.

What is a U-value and where can I find mine?

A U-value says how many watts flow through one square metre of a building part for each kelvin of temperature difference. Lower means better insulated. Look in an energy certificate, a building survey, or the data sheet of the window or insulation product.

Can I use Fahrenheit for the temperature?

Yes, but only for the difference between inside and outside, such as 36 degrees F. The tool multiplies it by 5/9 to get kelvin. Do not enter 68 for room temperature and expect the tool to subtract the outdoor value for you.

Why do I have to type zeros for parts I do not have?

Every box is required, and the calculation reads all four parts. Entering 0 for an area and 0 for its U-value tells the tool that the part adds nothing. Leaving a box empty makes the tool show an input error.

Can I size a heater or heat pump with this?

No. Choosing equipment needs a full load calculation that covers design temperatures, thermal bridges, orientation, local rules and more. This page is a simplified estimate for comparison and learning, and it says so on the page itself.

Why is my result different from my energy bill?

A bill reflects real weather, how long and how warmly you heat, free heat from people and the sun, and how efficient your system is. This tool shows one steady moment at one temperature gap, so the two numbers measure different things.

Are my room measurements sent anywhere?

No. The calculation runs in your browser, and the numbers are not uploaded or saved by the tool. Nothing is kept for later, so use Copy estimate if you want to keep the rows.

What does the BTU/h figure mean?

It is the same heat-loss rate as the watt total, converted with 1 W = 3.412141633 BTU/h. Some heating equipment and older documents use BTU/h, so the tool shows both next to each other for convenience.

How do you calculate heat loss through a building component?

For transmission, multiply area by U-value and temperature difference: watts = m² × W/(m²·K) × K. A component with U = 1, area 10 m² and a 20 K difference contributes 200 W. Ventilation is estimated separately from room volume and air changes.

Are my room measurements uploaded?

No. This estimate runs locally in your browser; your inputs are not sent to a server or saved by this tool.

Is a temperature difference in Fahrenheit converted like a normal temperature?

No. A Fahrenheit temperature difference is multiplied by 5/9 to convert to kelvin difference; an offset is not added.

Can I use this to choose a furnace or heat pump?

No. It is a simplified component estimate and does not include all design conditions or local standards. Heating equipment selection needs a complete, qualified load assessment.